Motor Connecting Cables | |||
2YSLCY-JB/2YSLCYK-JB | 9YSLCY-JB | PENDANT CABLE |
Mineral insulated cables
Heating Tape for Sensitive Surfaces
Application
Heat tracing on apparatus, appliances and systems
Temperature maintenance on piping
Laboratory applications
Standard
DIN VDE 0253
Voltage Rating
230V
CABLE CONSTRUCTION
Heating conductor
Insulation: Fluoropolymer.
Protective: Nickel-plated copper.
Outer sheath: E-glass textile.
Mechanical and Thermal Properties
Maximum operating temperature: 260℃
Minimum installation temperature: -60℃
Minimum bending radius flat: 10 mm
Maximum output: 50 W/m
Approx Dimensions : 25 x 6 mm
Cable Parameter
Heated length m |
Nominal output W |
||
---|---|---|---|
Maximum temperature 100 °C |
Maximum temperature 150 °C |
Maximum temperature 200 °C |
|
0.6 |
30 |
- |
- |
1.1 |
54 |
- |
- |
1.7 |
78 |
52 |
26 |
2.4 |
94 |
69 |
37 |
3.0 |
147 |
88 |
44 |
4.2 |
210 |
126 |
63 |
5.4 |
245 |
163 |
82 |
6.0 |
294 |
176 |
88 |
7.0 |
344 |
- |
- |
10.0 |
464 |
294 |
- |
12.5 |
623 |
371 |
192 |
15.0 |
705 |
441 |
220 |
17.5 |
864 |
521 |
- |
21.0 |
1008 |
611 |
315 |
28.0 |
1390 |
756 |
378 |