Motor Connecting Cables
2YSLCY-JB/2YSLCYK-JB 9YSLCY-JB PENDANT CABLE  

Mineral insulated cables

Heating Tape for Sensitive Surfaces

Application

Heat tracing on apparatus, appliances and systems

Temperature maintenance on piping

Laboratory applications

Standard

DIN VDE 0253

Voltage Rating

230V

CABLE CONSTRUCTION

Heating conductor

Insulation: Fluoropolymer.

Protective: Nickel-plated copper.

Outer sheath: E-glass textile.

Mechanical and Thermal Properties

Maximum operating temperature: 260℃

Minimum installation temperature: -60℃

Minimum bending radius flat: 10 mm

Maximum output: 50 W/m

Approx Dimensions : 25 x 6 mm

Cable Parameter

 

Heated length m

Nominal output W

Maximum temperature 100 °C

Maximum temperature 150 °C

Maximum temperature 200 °C

0.6

30

-

-

1.1

54

-

-

1.7

78

52

26

2.4

94

69

37

3.0

147

88

44

4.2

210

126

63

5.4

245

163

82

6.0

294

176

88

7.0

344

-

-

10.0

464

294

-

12.5

623

371

192

15.0

705

441

220

17.5

864

521

-

21.0

1008

611

315

28.0

1390

756

378